Special Edition

Ventilation, Vaccination, Infection, and Luck. Covid-19 and the New Year

Goodbye, 2020!

We wish you a happy holiday season and a much, much brighter New Year! 2021 should bring Covid-19 under control. Our seemingly endless battle with SARS-CoV-2, and with ourselves, will not go away easily, however, and we are still at the beginning of the war with Covid-19.

The indoor environment is the battleground, and today’s inadequate ventilation and air filtration standards are Covid-19’s primary weapon.

Four interrelated effects determine our path through the pandemic:

• Ventilation

• Vaccination

• Infection

• Luck (both good and bad)

As we wrote in our March 2020 news article, SARS-CoV-2 is an airborne disease. CDC and ASHRAE now acknowledge and agree with Build Equinox recommendations described in our May 2020 news article, however, they continue to leave the specifics of “increased ventilation” and air filtration unspecified. How much fresh air is needed? What air recirculation flow through improved filters is good? How much do face masks help? These are the specifics Build Equinox works to answer, and has for many years.

Anyone entering a building without knowing its air quality is playing Russian roulette with their health. Our noses cannot smell healthy, contagion-free air. The odor of disinfectant is no assurance of a virus-free space.

People in the US and many other countries are unfortunately acting in a divided manner. Some people are choosing to follow a pro-active path to protect themselves, their families and friends from the disease. Protective measures must continue for at least the first 6 months of the new year when “herd immunity” (aka, herd protection) through vaccination and recovered infection cases reach a level that dampens disease transmission.

The fraction of a country’s populace choosing to ignore precautions will follow the infection path. The vaccine protection path is the more economical path as well as the one that harms fewer people. Unfortunately, a significant number of people have decided that their 90% chance of experiencing minor symptoms outweighs consideration for the remaining 10% who will experience a debilitating illness and the 1% of a community who will die. The cost difference is enormous. As much as it seems that 15,000,000 and counting infections must be near the end, herd protection will not occur until 200,000,000 more people in the US are either vaccinated or infected. At $20 per vaccine dose, the cost for vaccinated herd protection is $4billion. Following the infection route, with 10% (20,000,000) of the infected population becoming severely ill (and 10% of those die), at $50,000 per severe illness, the cost of infected herd immunity is $1trillion. The real answer is somewhere between these levels, and our behavior determines whether we spend $4B or $1T.

Some of cautious folks and some callous folks will be lucky. Some of the luck will be good (careless folks who do not become infected) and some of the luck will be bad (cautious folks who are infected). Spectacular news of multiple, highly effective vaccines provide hope for the new year that those who choose to be vaccinated can avoid the disease’s devastation.

How does vaccination and immunity from infection recovery combine to create the so-called “herd immunity”. The herd immunity concept is a statistical description rather than an individual one. Herd immunity signifies the condition where a disease is no longer self-propagating, however, outbreaks will continue to occur. One group can get “heads” 100 times in a row while another can toss 100 “tails” in a row. Overall, the probability is still 50% heads and 50% tails.

Like tossing a coin, one building can inhibit disease transmission while another indoor space encourages transmission even though a community has reached herd immunity. Your health doesn’t have to be a coin toss. Following our guidelines for fresh air (800ppm carbon dioxide concentration), air recirculation through MERV13 filters, wearing face masks, and distancing creates a situation where you are not gambling with your health.

The table below from our May guidelines article shows how carbon dioxide concentration from respiration is related to fresh air flow through an indoor space. A house may have an average carbon dioxide concentration of 800ppm, however, if the occupied space is at 1200ppm and the unoccupied space is 400ppm, the occupants are at higher risk. Note that 1200ppm, typical of indoor spaces at today’s standard ventilation rates, has half the fresh air flow (20cfm per person of fresh air flow) as our recommended 800ppm with 40cfm of fresh air per occupant.

The building schematic below shows a generalized model Build Equinox has developed for assessing the effects of vaccination and infection on susceptible persons. Included in the model are the effects of two air recirculation systems (eg, the building ventilation system and a localized space filtration unit). The model includes the impact of human behavior (ie, wearing face masks).

Schematic of general model for predicting probability of SARS-CoV-2 infection and determining if the disease is self-propagating based on fresh air ventilation, air recirculation filtering and UVGI, face mask usage, susceptible people, infectious people, and immune people.

Face masks are important for two reasons:

1) Reduction of contagion emitted by contagious persons

2) Filtration of contagion inhaled by susceptible persons

Note that contagion filtration efficiencies of exhalation and inhalation can be different. Also, if an ideal face mask had been developed in parallel with vaccines, all airborne contagion could be removed and killed before a susceptible person inhaled it. How could sophisticated vaccines be developed, but high performance N95 masks are still not available after 9 months?

Several figures below display the probability of a susceptible person becoming infected, and the very important “building Reproduction number” (building Ro). These terms are discussed in our original March article on Covid-19 and airborne disease transmission. While we may be most interested in our chance of getting infected, Ro is more important because it indicates when we reach herd immunity. Ro is the ratio of people infected per infectious person, and when Ro is less than 1, a disease is no longer self-sustaining. Ro is not a constant value even though you may hear that it has an average value of 2 to 3. Our habits, the building environment, the weather and other factors impact Ro.

Probability of infection in a building versus carbon dioxide concentration for 1 hour exposure. No air recirculation filtering and sanitizing (UVGI) assumed with 5, 10, and 100 occupants (with 1 occupant infectious and all others susceptible). Note that standard ventilation (1200ppm, or 20cfm fresh air per occupant) is 50% more likely to infect people than 800ppm (40cfm per occupant). More importantly, note that Ro for 800ppm is less than 1 while 1200ppm is greater than 1, indicating self-sustained disease propagation.
Recirculating air at 25cfm per occupant through a MERV 13 filter reduces infections and reduces Ro below 1 for a 1 hour exposure time. The cost for added fresh air (without energy recovery) is a penny per hour of occupancy when it is freezing outside, and you are worth a penny per hour! The cost for air recirculation and improved filtration? Less than a penny per hour of occupancy.
These plots show an 8 hour exposure time with no air recirculation and filtration. 800ppm significantly reduces probability of infection compared to standard (1200ppm) ventilation, however, the disease remains above 1.
Adding 25cfm per person of air recirculation through a MERV 13 filter significantly reduces probability of infection over an 8 hour exposure time, however, building Ro continues to remain above 1 at self-sustaining disease transmission levels.
An 8 hour exposure with occupants wearing face masks with 50% exhalation filtration capture of contagion from infectious persons and 50% inhalation filtration of contagion by susceptible persons in the room, coupled with 25cfm per occupant of air recirculation through a MERV 13 filter further reduces the chance of becoming infected and reduces building Ro below 1 (self-sustained transmission) at 800ppm carbon dioxide concentration.
75% occupant immunity (sum of vaccinations and recovered immunities) does not reduce your chance of becoming infected if you’re susceptible, however, the building Ro is reduced. The above case assumes 8 hour exposure time with air recirculation at 25cfm per person through a MERV 13 filter.

Plots showing a susceptible person’s infection probability and the building Ro are shown for the following cases:

1) 5, 10, and 100 occupants with 1 infectious occupant during 1 hour exposure time. Infection probability and building Ro are shown versus indoor air carbon dioxide concentration (800ppm = 40cfm fresh air per occupant; 1200ppm = 20cfm fresh air per occupant).

2) Same as Case 1 with 25cfm per person air recirculation through a MERV 13 filter

3) Same as Case 1 but for 8 hour exposure time

4) Same as Case 2 but for 8 hour exposure time

5) Same as Case 4, but with face masks usage that reduces exhalation contagion from infectious persons by 50%, and 50% contagion inhalation filtration for susceptible persons, similar to today’s cloth/paper masks

6) Same as Case 4 but 75% of occupants are immune from vaccinations or recovered infections.

The series of cases can be summed up as follows: doubling fresh air ventilation from today’s standard ventilation significantly reduces your chances of becoming infected if an infectious person enters the space. More importantly, increased fresh air ventilation can reduce contagion transmission below self-sustaining levels at low exposure times (1 hour). Adding air recirculation through a MERV 13 filter at 25 cfm per occupant further reduces both probability of infection and transmission replication. Lower Ro’s speed the decay of disease transmission.

8 hour exposure time periods, such as in the workplace, school or home, rely on face mask usage in combination with increased fresh air and improved air recirculation filtration to drop infection transmission to non-sustaining levels.

Self-sustained disease transmission is reduced as immunization increases, however, the probability of infection for susceptible occupants stays the same. A susceptible (unimmunized) person in a room with 5 occupants (1 infectious person) has the same probability of becoming infected whether or not the other 3 people are immune or susceptible.

What are typical carbon dioxide levels in real buildings? We have been measuring carbon dioxide in many different situations for many years. Over the past year, an army of CO2 monitoring folks have been sending us pictures of places they visit (church, massage therapist, department stores, food pickup, etc). The 12 representative photos show CO2 levels above 1000ppm are prevalent (8 out of 12 situations shown). And, you could safely wager a few beers that recirculation filtration in these venues is poor or non-existent.

Carbon dioxide concentration readings in several venues. Do you think your nose can tell you which ones have sufficient fresh air? Are you willing to risk your health on it?

Following the CO2 photos are a series of carbon dioxide plots from different indoor environments. “Leaky”, older homes and high performance Passive House homes that meet today’s ventilation standards have poor carbon dioxide levels that efficiently transmit SARS-CoV-2 and influenza virus, as well as impair cognition and degrade sleep.

Carbon dioxide concentration in “leaky”, 1950s era house is too high, especially in bedrooms.
Carbon dioxide in certified Passive House is just as poor as in the leaky, 1950’s house because of inadequate ventilation standards (0.3ACH). Excessive pollutants when occupied and over-ventilated when unoccupied.
What’s the air quality at your workplace? Is a penny per hour per employee too much to keep people healthy? This 120 employee business has loss productivity and extra sick days because of poor IAQ.
House of worship gatherings are often not designed for proper ventilation during worship services, resulting in Covid-19 super-spreading.
Airline boarding bridges, such as this one at a major US airport, often have very poor ventilation. Loading has worse IAQ than unloading periods. And the aircraft not much better despite what airline CEOs state. Airlines; measure your carbon dioxide and display it to us!
An Illinois Department of Motor Vehicles (DMV) building with DCV (Demand Control Ventilation) that increases fresh air when carbon dioxide concentration increases above 1000ppm.

Office environments, houses of worship, and transportation centers have dynamic changes of air quality that require smart technologies to maintain a healthy indoor environment. The Illinois Department of Motor Vehicle facility plot shows how a DCV (Demand Controlled Ventilation) system responds to occupancy loading automatically. The carbon dioxide setting is too high per our guidelines, but the ability to change air quality is a simple movement of a dial.

Is our 800ppm too drastic of an increase in fresh air ventilation? Is saving a Btu more important than saving a life? How much does 800ppm ventilation control cost? Why not 1000ppm (~30cfm per occupant)? Our May guidelines provides background information and references for 800ppm fresh air ventilation. We listed two primary factors to set this standard. First, the study by Milton and colleagues (see reference on our website) with over 3000 employees scattered among several building environments demonstrated a 40% reduction of sick days in the workplace by doubling today’s ventilation standard, which is equivalent to the efficacy of the influenza vaccine. Although Covid-19 and the flu are two very different diseases, their transmission characteristics are similar (Ro ~2 to 3 on average). Second, cognition studies (see two TH Chan School of Public Health, Harvard University references on our website) indicate significant human productivity cost benefits with doubling today’s fresh air ventilation rates.

We do not know if 800ppm is low enough for Covid-19, however, 1000ppm was found in one study to be insufficient. A Dutch nursing home had rampant SARS-CoV-2 transmission in a carbon dioxide ventilation-controlled building with 1000ppm setpoint. The building did not have recirculation filtration of air as we recommend. As indicated by our prediction results, 1000ppm is expected to cause self-sustained disease transmission.

The cost? If it is freezing outside (32F or 0C), the utility cost for doubling fresh air is a penny per occupant hour! Although energy efficiency is important, your health is more important. IAQ is very dynamic. When you’re home, you need fresh air. Wherever you go and whatever you do, you must have fresh air. You need 10 times more fresh air when you’re exercising than when you’re asleep. As displayed in the carbon dioxide plots below, air quality is more complex than heating and cooling. In the new year, a new building design paradigm is needed, one in which all buildings place human health, well-being and productivity first among all other considerations. And that’s why we’ve developed CERV2 smart ventilation technologies. To provide a piece of mind and remove stress and worry about your indoor environment so you can be busy enjoying life!

Share

Subscribe to Newsletter

Archives

Filter
DateTitle
April 19, 2021 Spotlight – Illinois ADAPTHAUS Wins 1st Place in Comfort & Environmental Quality 20210419
April 19, 2021 Events – Register for Building Energy Boston (Online)! May 5-7 20210419
April 19, 2021 Featured Article – Broken Clocks Work Better than Today’s Ventilation Standards 20210419
April 19, 2021 Events – Upcoming Online Webinars and Conferences! 20210419
March 11, 2021 News – New Video, Booklet, and CERV2 Smart Options! 20210311
March 10, 2021 Spotlight – CERV Installed in the UofI ADAPTHAUS 20210310
March 10, 2021 Events – Re-Opening Schools and Beyond Safely Webinars (3/23, 4/21, 4/22) 20210310
March 10, 2021 Featured Article – Human Value: Thinking Beyond Energy 20210310
February 26, 2021 Spotlight – Dar-Lon Chan’s Journey to Sustainable Living 20210226
February 26, 2021 Featured Article – Covid Safe Space Calculator 20210226
January 29, 2021 Events – Efficiency Vermont Better Buildings by Design Conference (Feb 2-4) 20210129
January 29, 2021 Spotlight – University of Illinois ADAPTHAUS becoming Reality 20210129
January 29, 2021 Featured Article – CERV2 Installed in Equinox House! 20210129
December 21, 2020 Spotlight – Tour Bill Spohn’s New Modular Net Zero Home (CEUs available!) 20201221
December 21, 2020 Special Edition – Ventilation, Vaccination, Infection, and Luck. Covid-19 and the New Year 20201221
December 21, 2020 Featured Article – AWE: Air, Water, Energy 20201221
November 17, 2020 Events – CERV2 Smart-er Ventilation Product Demo (Video + PDF) 20201117
November 16, 2020 Spotlight – New Lungs for a 101-Year-Old Home Pt.3: Heat Pump Water Heater! 20201116
November 15, 2020 Featured Article – Equinox Meets the Needs / ASHRAE Solar ZEB Article 12 20201115
November 12, 2020 Special Edition – Stay Safe this Holiday Season! 20201112
October 29, 2020 Spotlight – New Lungs for a 101-Year-Old Home Pt.2: Total HVAC Replacement! 20201029
October 28, 2020 Featured Article – Equinox House Performance / ASHRAE Solar ZEB Article 10 20201028
September 22, 2020 Events – Michigan Residential Net Zero Energy Conference (Oct 20-22) 20200922
September 22, 2020 News – CERV-UV Now Available for New Orders! 20200922
September 22, 2020 News – CERV-ICE Now in the iOS and Android App Stores! 20200922
September 22, 2020 Featured Article – Solar Collection & Use / ASHRAE Solar ZEB Article 10 20200922
August 17, 2020 Special Edition – Build Equinox Groundbreaking Research into COVID 19 20200817
August 17, 2020 Events – SEDAC Webinar: Considerations, Best Practices, and Energy Implications for Reopening Critical Community Facilities in the Pandemic (Aug 18, 2020) 20200817
August 17, 2020 Featured Article – Comfort Conditioning & Indoor Air Quality / ASHRAE Solar ZEB Article 9 20200817
August 17, 2020 News – Building Science Podcast: “Ventilation & Virus Transmission Prevention” 20200817
August 14, 2020 News – New HVAC School Podcast: “Advanced Ventilation w/ CERV2” (Watch/Listen) 20200814
August 12, 2020 Events – Free CEU Webinar: Can Building Science Help Us Slow COVID-19? (Sep 2, 2020) 20200812
July 10, 2020 Tech – Ultimate Ultraviolet! 20200710
July 10, 2020 Special Edition – Covid-19 Update: Airborne Means AIRBORNE! 20200710
July 10, 2020 Featured Article – Appliances Power EVs / ASHRAE Solar ZEB Article 8 20200710
June 29, 2020 Events – Free New Webinar: Guidelines for Protecting Against COVID-19 (PDF + Slides) 20200629
June 25, 2020 Featured Article – Designing a Thermally Massive Home/ASHRAE Solar ZEB Article 7 20200625
June 25, 2020 Special Edition – Covid19 Status Report: We are at the Beginning of the Pandemic, Not the End 20200625
May 29, 2020 Spotlight – CERV Retrofit: New Lungs for a 101-Year-Old Home 20200529
May 29, 2020 Special Edition – Covid19 Status Report: Guidelines for Homes & Businesses 20200529
May 29, 2020 Featured Article – Ground Heat Transfer/ASHRAE Solar ZEB Article 6 20200529
April 16, 2020 Events – Free CEU Webinar: Covid-19 Characteristics, Transmission, and Control (April 29th) 20200416
April 16, 2020 Special Edition – Battling the Spread of Covid-19 20200416
April 16, 2020 Featured Article – Infiltration & Sealing/ASHRAE Solar ZEB Article 5 20200416
April 16, 2020 Spotlight – New Projects: 1930s CERV Retrofit & Mitsubishi Hyperheat 20200416
March 13, 2020 Featured Article – Light and Delight/ASHRAE Solar ZEB Article 4 20200313
March 10, 2020 News – CERV Voted One of the Top 16 Coolest Things Made in Illinois! 20200310
March 5, 2020 Special Edition – Fighting COVID-19 with Fresh Air 20200305
February 24, 2020 Featured Article – Walls and Roof/ASHRAE Solar ZEB Article 3 20200224
February 24, 2020 Tech – Magic-Box Mechanicals 20200224
February 24, 2020 Events – Designing Exceptional Homes for Exceptional People Webinar (Video + PDF) 20200224
January 30, 2020 Events – Visit us (Booth 17) at Energy Design Expo in Duluth (2/25-26) 20200130
January 14, 2020 Tech – Designing Exceptional Homes for Exceptional People 20200114
January 14, 2020 Featured Article – Designing for Zero/ASHRAE Solar ZEB Article 2 20200114
December 19, 2019 Events – Free Webinar: Smart Ventilation & Air Distribution (Video+PDF) 20191219
December 19, 2019 Events – CERV2 Smart-er Ventilation Product Demo (Video + PDF) 20191219
December 19, 2019 Spotlight – Acorn Glade: 2019 NAPHC Awardee! 20191219
December 16, 2019 Featured Article – Equinox Origins/ASHRAE Solar ZEB Article 1 20191216
November 19, 2019 Events – Visit our booth at 2019 NAPHC in Washington DC! 20191119
November 19, 2019 Spotlight – Equinox House Turning 10! 20191119
November 19, 2019 Featured Article – Handling Humidity Pt.4 Putting it All Together 20191119
October 16, 2019 Events – Mechanical Systems for Passive Buildings (Chicago, Oct 16) 20191016
October 16, 2019 Featured Article – Handling Humidity Pt.3 Methods for Managing Moisture 20191016
October 16, 2019 Events – Free Webinar: Handling Humidity (Video + PDF) 20191016
October 16, 2019 Events – Free CEUs: Building Green & Beer at Founders Brewing (Oct 28) 20191016
October 16, 2019 Spotlight – Inter House Wins Solar Decathlon Africa!!! 20191016
September 20, 2019 Featured Article – Handling Humidity Pt.2 Climate Moisture Variations 20190920
September 20, 2019 News – Brand New Release: Colorfil VOC Absorbing Filters! 20190920
September 20, 2019 Tech – From CERV to CERVEZA: a Quest for Smart Beer 20190920
August 27, 2019 Events – Earn Free CEUs with the Handling Humidity Webinar (Aug 29) 20190827
August 27, 2019 Featured Article – Handling Humidity Report Series 20190827
August 12, 2019 News – Listen to the Building HVAC Science Podcast, ft. Ty Newell! 20190812
July 29, 2019 Events – CERV2 Smart-er Ventilation Product Demo (Aug 27, 2019) 20190729
July 29, 2019 Featured Article – Poor Home Maintenance = Increased Health Risks 20190729
July 29, 2019 Tech – Say Hello to Our New Server! 20190729
June 19, 2019 Featured Article – Watch out for Cranky Heaters! 20190619
June 19, 2019 Events – Free CEU Webinar: Smart Ventilation & Air Distribution (July 10) 20190619
June 19, 2019 Spotlight – Marrakech Express! CERV2 Heading to Africa! 20190619
May 13, 2019 Featured Article – Taylor Home CERV Testimonial 20190513
May 13, 2019 Events – 7 Steps for Designing an Economical Net Zero Home (Video + PDF) 20190513
May 13, 2019 Tech – AeroBarrier Demonstration 20190513
April 15, 2019 Events – Indoor Air Quality Metrics Free Webinar (Apr 24, 2019) 20190415
April 15, 2019 Featured Article – CERV2 Geo–Boost 20190415
April 15, 2019 Review – 2019 National Home Performance Conference 20190415
April 15, 2019 Tech – CERV2 Sketchup Model Now Available 20190415
March 28, 2019 News – Visit us at the Chicago 2019 National Home Performance Conference 20190328
March 28, 2019 Featured Article – Happy Equinox, St. Patrick’s Day, and Super Moon! 20190328
February 27, 2019 Events – Free CEU Webinar: Smart Ventilation & Air Distribution (Mar 12) 20190227
February 27, 2019 Featured Article – Smart Ventilation and Smart Air Distribution Reports 20190227
February 27, 2019 Spotlight – El Salvador NZEB Update 20190227
February 25, 2019 Events – CERV2 Smart-er Ventilation Product Demo (Video + PDF) 20190225
January 22, 2019 Events – Smart Ventilation & Smart Air Distribution Webinar (Video & PDF) 20190122
December 26, 2018 Spotlight – Progressive Canada 20181226
December 26, 2018 News – Happy Holidays from Build Equinox! 20181226
December 26, 2018 Review – CERV2 at Greenbuild 2018 20181226
November 26, 2018 News – CERV OEM Filter Store is OPEN!!! 20181126
November 19, 2018 News – Check Out Our Social Media! 20181119
October 24, 2018 Events – Free CEU Webinar: Duct Design & Performance (PDF Download) 20181024
October 24, 2018 Featured Article – CERV2 is UL Approved! 20181024
October 24, 2018 News – Stop by Our Booth at Greenbuild Chicago (Free Tickets!) 20181024
October 24, 2018 Spotlight – University of Illinois Students Visit Build Equinox 20181024
July 23, 2018 Featured Article – Happy 10th Birthday, CERV and Sunflower! 20180723
July 23, 2018 Spotlight – Good News from El Salvador! 20180723
June 22, 2018 Tech – Installing a Ductless Mini-split 20180622
June 22, 2018 Featured Article – Mini-split Mania! 20180622
April 30, 2018 News – Now offering on-demand webinars for CEUs! 20180430
April 30, 2018 Events – Free CEU Webinar! (May 2, 2018) 20180430
April 30, 2018 Featured Article – Ductology Part 2 20180430
February 19, 2018 Review – 2018 Better Buildings by Design Conference, Flu and Colds 20180219
February 19, 2018 Featured Article – Hot Water! 20180219
January 22, 2018 Events – Visit us at BuildingEnergy Boston! (March 7-9, Boston, MA) 20180122
January 22, 2018 Events – Efficiency Vermont Better Buildings by Design Conference (Feb 7-8) 20180122
January 22, 2018 Featured Article – Ductology (Part 1) 20180122
November 20, 2017 Featured Article – Heat Pump (Hybrid) Clothes Dryers are Coming! 20171120
October 31, 2017 Featured Article – CERV2 Measures IAQ at NAPHC & NAPHN 20171031
September 25, 2017 Featured Article – Introducing CERV2 20170925
August 21, 2017 Events – Free CEU Webinar! (Sep 27, 2017) 20170821
August 21, 2017 Featured Article – Quiz 20170821
July 27, 2017 Events – New IAQ Metrics Webinar (Video + PDF) 20170727
July 25, 2017 Featured Article – Endotoxins: Small But Very Significant 20170725
May 22, 2017 Events – Economical Net Zero Design Webinar (Video+PDF) 20170522
May 22, 2017 Featured Article – Styrax Japonicus 20170522
April 28, 2017 Events – 7 Steps for Designing an Economical Net Zero Home (May 25) 20170428
April 28, 2017 Featured Article – Engineering Net Zero Homes 20170428
March 20, 2017 Featured Article – Build Equinox Zero Plus Facility 20170320
February 14, 2017 Featured Article – February Flu 20170214
January 20, 2017 Events – HRV, ERV and Smart Vent Systems, Free CEU Webinar (Feb 15) 20170120
January 20, 2017 Events – NESEA IAQ Metrics Presentation (Mar 9, Boston, MA) 20170120
January 19, 2017 Featured Article – The Perfect Dust Storm 20170119
January 12, 2017 Events – Efficiency Vermont Better Buildings by Design Conference (Feb 1-2) 20170112
December 26, 2016 Featured Article – Happy Holidays from Build Equinox! 20161226
November 29, 2016 Featured Article – Geo-Boost 20161129
November 29, 2016 Spotlight – This Old Passive House 20161129
November 29, 2016 Review – House Music 20161129
October 28, 2016 Featured Article – Comparing ERV, HRV, and CERV 20161028
October 28, 2016 Spotlight – Net Zero Eco-House (Monticello, IL) 20161028
October 28, 2016 Spotlight – Forty Under 40 20161028
September 28, 2016 Events – Free CEU Webinar (Oct 5th): Why are new Indoor Air Quality metrics needed? 20160928
September 28, 2016 Review – 2016 North American Passive House Conference 20160928
September 28, 2016 Featured Article – New CERV-ICE IAQ Analytics Released! 20160928
September 28, 2016 Spotlight – CERVs in Passive Homes, pt. 2 20160928
August 18, 2016 Featured Article – Understanding the House as a System 20160818
August 18, 2016 Spotlight – CERVs in Passive Homes 20160818
August 18, 2016 Review – “What is IAQ?”, P. Ole Fanger 20160818
August 18, 2016 Tech – CERV CO2/VOC Library 20160818
July 19, 2016 Events – September North American Passive House Conference 20160719
July 18, 2016 News – CERV Website 20160718
July 18, 2016 Featured Article – VERMOD CERV Report Released 20160718
July 18, 2016 Review – LBNL report: “Houses are Dumb Without Smart Ventilation” 20160718
July 18, 2016 Spotlight – Professor P. Ole Fanger (1934-2006); IAQ and Comfort Pioneer 20160718
July 18, 2016 Tech Note – Airflow Calculation for Ventilation Systems 20160718
Call 1-773-492-1893
Visit 1103 N. High Cross Rd. Urbana, IL 61802
Email moc.xoniuqedliub@ofni
Follow
About Learn More about us!
© Build Equinox 2021